KEBOS POWER ,to continue a better life.
Low Frequency Online UPS built-in isolation transformer, it will eliminates common mode noise and the need to install expensive dedicated circuits.
GL11 series single phase Low Frequency UPS provides reliable galvanically isolated power to critical equipment.
Galvanic isolation design to withstand all kinds of load
Output power factor 0.8
Fully coating PCBAs to withstand harsh environment
Unique ventilation design for effective heat dissipation
Wide input voltage and frequency range to withstand robust environment
High short-circuit and overload capabilities
Built-in Maintenance bypass switch
MODEL | GL11 Lite-6K(L) | GL11 Lite-7.5K(L) | GL11 Lite- 10K(L) | ||||
---|---|---|---|---|---|---|---|
PHASE | Single phase with ground | ||||||
Capacity* | 6KVA/4.8KW | 7.5KVA/6KW | 10KVA/8KW | ||||
INPUT | |||||||
Nominal Voltage | 208VAC/220VAC/230VAC | ||||||
Voltage Range | 165VAC ~ 285VAC @ 16 pcs of batteries 185VAC ~ 285VAC @ 18 pcs of batteries | ||||||
Frequency Range | 40Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64 Hz @ 60Hz system | ||||||
OUTPUT | |||||||
Output Voltage | 208VAC/220VAC/230VAC | ||||||
Voltage Regulation | ± 1% | ||||||
Frequency Range (Synchronized Range) | 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz | ||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||||
Current Crest Ratio | 3:1 | ||||||
Harmonic Distortion | ≦ 3 % THD (Linear Load) ≦ 5 % THD (Non-linear Load) | ||||||
Transfer Time | AC to DC | Zero | |||||
Inverter to Bypass | Zero | ||||||
Wave Form (Batt. Mode) | Pure Sine Wave | ||||||
EFFICIENCY | |||||||
AC Mode | 88.3% | ||||||
Battery Mode | 92% | ||||||
BATTERY | |||||||
Standard Model | Battery Type | 12V / 9Ah | |||||
Battery Numbers** | 16 pcs | ||||||
Recharging Time | 6 hours recover to 90% capacity | ||||||
Charging Current (max.) | 2A | ||||||
Charging Voltage | 218.4 V ± 1% | ||||||
Long-run Model | Battery Type | Depending on the applications | |||||
Numbers | 16pcs | 18 pcs | 16pcs | 18 pcs | 16pcs | 18 pcs | |
Charging Current (max.) | Default :8 A; 2A/4A/8A(Adjustable) | ||||||
Charging Voltage | 218.4 V ± 1% | 245.7 V ± 1% | 218.4 V ± 1% | 245.7 V ± 1% | 218.4 V ± 1% | 245.7 V ± 1% | |
INDICATORS | |||||||
LCD | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code | ||||||
ALARM | |||||||
Battery Mode | Sounding every 4 seconds | ||||||
Low Battery | Sounding every second | ||||||
Overload | Sounding twice every second | ||||||
Fault | Continously sounding | ||||||
PHYSICAL | |||||||
Standard Model | Dimension, D X W X H (mm) | 592 x 300 x 826 | |||||
Net Weight (kgs) | 106 | 114 | 122 | 130 | 130 | 138 | |
Long-run Model | Dimension, D X W X H (mm) | 592 x 250 x 826 | |||||
Net Weight (kgs) | 62 | 78 | 86 | ||||
ENVIRONMENT | |||||||
Operation Temperature | 0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C) | ||||||
Operation Humidity | <95 % and non-condensing | ||||||
Noise Level | Less than 60dBA @ 1 Meter | ||||||
MANAGEMENT | |||||||
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC | ||||||
Dry Contact | Five signals: AC failure, low battery, UPS alarm, bypass and UPS fault | ||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
* Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC. | |||||||
**Battery number is set in factory and can't be changed by users. | |||||||
* Product specifications are subject to change without further notice |