APD Modular 33 60 ~ 140K LV

APD series is a high-performance, right-sized, Input and output low-voltage design Three-phase Modular Online UPS system which can easily scales in 60KW increments up to 140KW for any size data center or facility ,Offering High efficiency and overload capability.

The APD Modular Online UPS series is a world class, redundant, scalable, 3 Phase Online UPS power protection system designed to cost effectively provide high levels of availability. Seamlessly integrating into today's state-of-the-art data center designs, the APD Modular Online UPS series is a true modular system. 

Made up of dedicated and redundant modules--power module, STS module and battery module and bypass, all engineered into a design that is easily and efficiently serviceable, this architecture can scale power and runtime as demand grows or as higher levels of availability are required.

Highly manageable, the APD Modular Online UPS series features self-diagnostic capabilities and standardized modules which mitigate the risk of human error resulting in increased overall data center reliability.

  • N+1 or N+R Parallel Redundancy for power guarantee

  • Modular design decreases MTTR

  • High scalability

  • Built-in maintenance bypass switch for easy maintenance without interruptible

  • High efficiency double conversion online UPS

  • Adjustable charging current

  • Graphic 5.7'' LCD design for easy configuration

  • Option of 10" colorful touch screen LCD

Drag the table to right or left to view more.
MODELAP30U-60LVAP42U-80LVAP30U-80LVAP30U-120LVAP42U-140LV
PHASE3-phase in/3-phase out
CABINET CAPACITY*54KW72KW72KW108KW126KW
BATTERY TYPEBuilt-in BatteryExternal Battery
One Power Module Capacity20KVA/18KW
Max. Power Module No.34468
Max. Battery Set No.**34---
INPUT
Nominal Voltage3 x 208 VAC (3Ph+N)
Voltage Range156 ~ 253 VAC at 70% - 100% load; 121 ~ 253VAC for <70% load
Nominal Frequency50/60Hz (Auto sensing)
Frequency Range40Hz ~70Hz
Power Factor> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)< 3% @ 100% load
OUTPUT
Nominal Voltage3 x 208/220 VAC (3Ph+N)
Voltage Regulation (Steady state)≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
Voltage Regulation (Transient)≦± 5% Typical
Nominal Frequency50/60Hz
Frequency Range (Synchronized range)46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Harmonic Distortion≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load)  (PF = 0.8 ~ 1)
EfficiencyUp to 92.5% at over 50% load
BATTERY / CHARGER
Nominal Voltage+/- 120V (12V x 20 pcs)
Floating Charge Voltage2.3V/Cell
Boost Charging Voltage2.35V/Cell
Temperature CompensationYes
Maximum Charging Current8A for each power module (User-djustable)
PHYSICAL
Cabinet Dimension
(D x W x H) mm
1100 x 600 x 14751100 x 600 x 20101100 x 600 x 14751100 x 600 x 14751100 x 600 x 2010
Net Weight (kg)670.5926329428.57 Power Modules: 504
8 Power Modules: 537
ENVIRONMENT
Operation Temperature0 ~ 40℃
Relative Humidity0 ~ 95% non-condensing
Altitude ***<1000m for Nominal power
IP ClassIP 20
MANAGEMENT
RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
STANDARDS
SafetyUL1778, CSA C22.2 No. 107.3-05
EMCFCC Part 15,Subpart B Class A 
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃. 
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. 
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.