KEBOS POWER ,to continue a better life.

GHD & GRD 11 6-10KVA

GHD & GRD 11 6-10K is double-conversion high frequency online UPS with a output power factor 1.0 Ranging from 6KVA to 10KVA, It’s design in small footprints with DSP technology and active input power factor correction design to ensure better output voltage conditions, power quality and power performance at all times. Its dual mains inputs will secure the power reliability in power fluctuation area.

  • True double-conversion

  • DSP technology guarantees high performance

  • Output power factor 0.9

  • Wide input voltage range (60-150 VAC)

  • Active input power factor correction 0.99

  • 50Hz/60Hz frequency converter mode

  • Eco mode operation for energy saving (ECO)

  • Emergency power off function (EPO)

  • Generator compatible

  • Charger capacity expansion to 8A for long-run models

  • SNMP/USB/RS-232 communications

  • 3-stage extendable charging design for optimized battery performance

  • Maintenance bypass available

  • Adjustable battery numbers

Drag the table to right or left to view more.
MODELGHD11- 6K(L)GRD11- 6K(L)GHD11-10K(L)GRD11-10K(L)
PHASE2 phase in / 2 phase out
CAPACITY6000 VA / 5400 W10000 VA / 9000 W
INPUT
Nominal Voltage100/110/115/120/127 VAC (L-N)
Voltage Range 60-150 VAC (Phase-N) @ 50% load
80-140 VAC (Phase-N) @ 100% load 
Frequency Range46~54 Hz or 56~64 Hz
Phase Angle0°/120°/180°/240°
Power Factor≧ 0.99  @ 100% load
OUTPUT
Output Voltage100/110/115/120/127 VAC (L-N)
Phase Angle0°/120°/180°/240°
AC Voltage Regulation (Batt. Mode)± 1%
Frequency Range (Synchronized Range)46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≦ 2 % THD (Linear Load), ≦ 5 % THD (Non-linear Load)
Transfer TimeAC Mode to Battery ModeZero
Inverter to BypassZero
Inverter to ECO< 10ms
Wave Form (Batt. Mode)Pure Sine Wave
EFFICIENCY
AC Mode90.5%91.0%
ECO Mode96.0%
Battery Mode87.0%88.0%
BATTERY
Standard ModelBattery Type12 V / 7 AH12 V / 9 AH
Numbers10 pcs x 2 strings10 pcs x 2 strings
Typical Recharge Time5 hours recover to 90% capacity7 hours recover to 90% capacity
Charging Current (max.)2.0 A2.0 A
Float Charging Voltage136.5 VDC
Long-run ModelBattery TypeDepending on applications
Numbers
Charging Current (max.) 8.0 A
Float Charging Voltage136.5 VDC
INDICATORS
LCD PanelUPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinuously sounding
PHYSICAL
Standard ModelDimension, D X W X H (mm)592 x 250 x 576UPS unit:668 x 438 x 133(3U)
Battery pack: 580 x 438 x 133(3U)
592 × 250 × 826UPS unit:668 x 438 x 266(6U)
Battery pack: 580 x 438 x 133(3U)
Net Weight (kgs)83UPS unit: 22
Battery pack: 63
100UPS unit: 45
Battery pack: 63
Long-run ModelDimension, D X W X H (mm)592 x 250 x 576668 x 438 x 133(3U)592 x 250 x 576668 x 438 x 266(6U)
Net Weight (kgs)28223845
ENVIRONMENT
Operation Humidity0-95 % RH @ 0- 40°C (non-condensing)
Noise LevelLess than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
* L means long-run model