KEBOS POWER ,to continue a better life.
GHD33 III LV series Online UPS from 15K -100KVA, is specially designed with pluggable power module and front access to simplify maintenance. Its power walk-in function optimize parallel operation up to 6 units even with generator input.
True double-conversion
DSP technology guarantees high performance
Output power factor 1.0
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving (ECO)
Emergency power off function (EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers for long-run model
Maintenance bypass available
Parallel operation with commom battery
Power walk-in function
Optional isolation transformer offers full isolation and complete common mode noise rejection
MODEL | GHD33 III-15KL | GHD33 III-30KL | GHD33 III- 50KL | GHD33 III-60KL | GHD33 III-90KL | GHD33 III-100KL | |
---|---|---|---|---|---|---|---|
PHASE | 3-phase in/3-phase out | ||||||
CAPACITY | 15KVA/15KW | 30KVA/30KW | 50KVA/50KW | 60KVA/60KW | 90KVA/90KW | 100KVA/100KW | |
PARALLEL CAPABILITY | 4 | ||||||
INPUT | |||||||
Nominal Voltage | 3 x 208/220 VAC (3Ph+N) | ||||||
Voltage Range | 70-156 VAC @ 50% load ; 88-146 VAC @ 100% load | ||||||
Frequency Range | 40~70 Hz | ||||||
Power Factor | ≧ 0.99 @ 100% load | ||||||
Harmonic Distortion (THDi) | < 4% at full linear load | ||||||
OUTPUT | |||||||
Output Voltage | 3 x 208/220 VAC (3Ph+N) | ||||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | ||||||
Frequency Range (Batt. Mode) | 50/60 Hz ± 1% | ||||||
Current Crest Ratio | 3:1 (max.) | ||||||
Harmonic Distortion | ≦2% THD (Linear Load) ≦5% THD (Non-linear Load) | ||||||
Transfer Time | AC mode to Battery mode | zero | |||||
Inverter to Bypass | zero | ||||||
Wave Form (Batt. Mode) | Pure Sine Wave | ||||||
Overload Capability | 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% for 400ms | ||||||
BYPASS | |||||||
Nominal Voltage | 3 x 208/220 VAC (3Ph+N) | ||||||
Voltage Range | 305VAC~457VAC | ||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | ||||||
Overload Capability | 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% for 400ms | ||||||
EFFICIENCY | |||||||
AC Mode | 93.5% | ||||||
ECO Mode | 98.5% | ||||||
Battery Mode | 92.5% | ||||||
BATTERY | |||||||
Battery Type | Depending on application | ||||||
Numbers | 32~40 pcs (Adjustable) | ||||||
Charging Current (max.) | 1-12A, Adjustable | 1-18A, Adjustable | 2-36A, Adjustable | 3-54A, Adjustable | |||
Charging Voltage | +/-13.65V*N (N = 16~20) | ||||||
INDICATORS | |||||||
Touch color LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||||
ALARM | |||||||
Battery Mode | Sounding every 4 seconds | ||||||
Low Battery | Sounding every second | ||||||
Overload | Sounding twice every second | ||||||
Fault | Continuously sounding | ||||||
PHYSICAL | |||||||
Dimension, D X W X H (mm) | 815 x 300 x 1000 | 815 x 300 x 1000 | 974 x 600 x 1600 | ||||
Net Weight (kgs) | 74 | 87 | 241 | 286 | 286 | 382 | |
ENVIRONMENT | |||||||
Operation Temperature | 0-40°C | ||||||
Operation Humidity | <95% and non-condensing | ||||||
Altitude** | 0 ~ 1000m at full load | ||||||
Noise Level | Less than 65 dB @ 1 Meter | Less than 70 dB @ 1 Meter | Less than 75 dB @ 1 Meter | ||||
MANAGEMENT | |||||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC | ||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
**If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m. | |||||||
Product specifications are subject to change without further notice. |