KEBOS POWER ,to continue a better life.

KH-I-TX 20KW

Built-in isolation transformer

Built-in with isolation transformer,it purifies input power to connected devices.It can be operated in three different operation modes,on-grid,off grid and grid-tie with backup,depending on power requirements.

  • Pure sine wave output

  • Self-consumption and Feed-in to the grid

  • Programmable supply priority for PV, Battery or Grid

  • True galvanic isolation transformer design

  • User-adjustable charging current

  • Programmable multiple operation modes: Grid-tie, off-grid and grid-tie with backup

  • Built-in timer for various mode of on/off operation

  • Multiple communication for USB, RS-232, Modbus and SNMP

  • Monitoring software for real-time status display and control

Drag the table to right or left to view more.
MODELKH-I- TX-6KWKH-I-TX-10KWKH-I-TX-20KW
MAXIMUM PV INPUT POWER9,000W15,000W30,000W
RATED OUTPUT POWER6,000W10,000W20,000W
MAXIMUM CHARGING POWER6,000W10,000W20,000W
GRID-TIE OPERATION
PV INPUT (DC)
Nominal DC Voltage500 VDC720 VDC
Maximum DC Voltage750 VDC950 VDC
Start-up Voltage / Initial Feeding Voltage220 VDC / 250 VDC500 VDC / 550 VDC
MPP Voltage Range250 VDC ~ 700 VDC550 VDC ~ 900 VDC
Full power MPP Voltage Range450 VDC ~ 700 VDC625 VDC ~ 900 VDC
Number of MPP Trackers1
Maximum Input Current 20 Amp33 Amp48 Amp
GRID/UTILITY OUTPUT (AC)
Nominal Output Voltage230 VAC (P-N) / 400 VAC (P-P)
Output Voltage Range184 - 265 VAC per phase
Output Frequency Range47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz
Nominal Output Current8.7 A per phase14.3 A per phase29 A per phase
Power Factor> 0.99
EFFICIENCY
Maximum Conversion Efficiency (DC/AC)91%91%
OFF-GRID OPERATION
AC INPUT
AC Start-up Voltage120 - 140 VAC per phase
Auto Restart Voltage180 VAC per phase
Acceptable Input Voltage Range170 - 280 VAC per phase
Maximum AC Input Current20 A per phase30 A per phase40 A per phase
PV INPUT (DC)
Maximum DC Power9,000W15,000W30,000W
Maximum DC Voltage750 VDC950 VDC
MPP Voltage Range250 VDC ~ 700 VDC550 VDC ~ 900 VDC
Number of MPP Trackers1
Maximum Input Current 20 Amp33 Amp48 Amp
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage230 VAC (P-N) / 400 VAC (P-P)
Output Frequency50 Hz / 60 Hz (auto sensing)
Output WaveformPure sine wave
Efficiency (DC to AC)91%
HYBRID OPERATION
PV INPUT (DC)
Maximum DC Power9,000W15,000W30,000W
Nominal DC Voltage500 VDC720 VDC
Maximum DC Voltage750 VDC950 VDC
Start-up Voltage / Initial Feeding Voltage220 VDC / 250 VDC500 VDC / 550 VDC
MPP Voltage Range250 VDC ~ 700 VDC550 VDC ~ 900 VDC
Number of MPP Trackers1
Maximum Input Current 20 Amp33 Amp48 Amp
GRID/UTILITY OUTPUT (AC)
Nominal Output Voltage230 VAC (P-N) / 400 VAC (P-P)
Output Voltage Range184 - 265 VAC per phase
Output Frequency Range47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz
Nominal Output Current8.7 A per phase14.3 A per phase29 A per phase
Power Factor> 0.99
AC INPUT
AC Start-up Voltage120 - 140 VAC per phase
Auto Restart Voltage180 VAC per phase
Acceptable Input Voltage Range170 - 280 VAC per phase
Maximum AC Input Current20 A per phase30 A per phase40 A per phase
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage230 VAC (P-N) / 400 VAC (P-P)
Output Frequency50 Hz / 60 Hz (auto sensing)
Output WaveformPure sine wave
Efficiency (DC to AC)>91%
BATTERY & CHARGER
Nominal Battery Voltage192 VDC384 VDC
Maximum Charging Current32A52A50A
GENERAL
PHYSICAL
Dimension, D X W X H (mm)815 x 300 x 830559 x 320 x 909559 x 320 x 909
Net Weight (kgs)102115120
INTERACE
Communication PortRS-232/USB
Intelligent SlotOptional SNMP, GRPS, WIFI, Modbus cards available
ENVIRONMENT
Humidity0 ~ 90% RH (No condensing)
Operating Temperature-10 to 55°C
Altitude0 ~ 1000 m**
*These figures are based on VDE-4105 standard. All figures may vary depending on different AC voltage and country requirements.
** Power derating 1% every 100 m when altitude is over 1000m