KEBOS POWER ,to continue a better life.
Built-in isolation transformer
Built-in with isolation transformer,it purifies input power to connected devices.It can be operated in three different operation modes,on-grid,off grid and grid-tie with backup,depending on power requirements.
Pure sine wave output
Self-consumption and Feed-in to the grid
Programmable supply priority for PV, Battery or Grid
True galvanic isolation transformer design
User-adjustable charging current
Programmable multiple operation modes: Grid-tie, off-grid and grid-tie with backup
Built-in timer for various mode of on/off operation
Multiple communication for USB, RS-232, Modbus and SNMP
Monitoring software for real-time status display and control
MODEL | KH-I- TX-6KW | KH-I-TX-10KW | KH-I-TX-20KW | |
---|---|---|---|---|
MAXIMUM PV INPUT POWER | 9,000W | 15,000W | 30,000W | |
RATED OUTPUT POWER | 6,000W | 10,000W | 20,000W | |
MAXIMUM CHARGING POWER | 6,000W | 10,000W | 20,000W | |
GRID-TIE OPERATION | ||||
PV INPUT (DC) | ||||
Nominal DC Voltage | 500 VDC | 720 VDC | ||
Maximum DC Voltage | 750 VDC | 950 VDC | ||
Start-up Voltage / Initial Feeding Voltage | 220 VDC / 250 VDC | 500 VDC / 550 VDC | ||
MPP Voltage Range | 250 VDC ~ 700 VDC | 550 VDC ~ 900 VDC | ||
Full power MPP Voltage Range | 450 VDC ~ 700 VDC | 625 VDC ~ 900 VDC | ||
Number of MPP Trackers | 1 | |||
Maximum Input Current | 20 Amp | 33 Amp | 48 Amp | |
GRID/UTILITY OUTPUT (AC) | ||||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |||
Output Voltage Range | 184 - 265 VAC per phase | |||
Output Frequency Range | 47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz | |||
Nominal Output Current | 8.7 A per phase | 14.3 A per phase | 29 A per phase | |
Power Factor | > 0.99 | |||
EFFICIENCY | ||||
Maximum Conversion Efficiency (DC/AC) | 91% | 91% | ||
OFF-GRID OPERATION | ||||
AC INPUT | ||||
AC Start-up Voltage | 120 - 140 VAC per phase | |||
Auto Restart Voltage | 180 VAC per phase | |||
Acceptable Input Voltage Range | 170 - 280 VAC per phase | |||
Maximum AC Input Current | 20 A per phase | 30 A per phase | 40 A per phase | |
PV INPUT (DC) | ||||
Maximum DC Power | 9,000W | 15,000W | 30,000W | |
Maximum DC Voltage | 750 VDC | 950 VDC | ||
MPP Voltage Range | 250 VDC ~ 700 VDC | 550 VDC ~ 900 VDC | ||
Number of MPP Trackers | 1 | |||
Maximum Input Current | 20 Amp | 33 Amp | 48 Amp | |
BATTERY MODE OUTPUT (AC) | ||||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |||
Output Frequency | 50 Hz / 60 Hz (auto sensing) | |||
Output Waveform | Pure sine wave | |||
Efficiency (DC to AC) | 91% | |||
HYBRID OPERATION | ||||
PV INPUT (DC) | ||||
Maximum DC Power | 9,000W | 15,000W | 30,000W | |
Nominal DC Voltage | 500 VDC | 720 VDC | ||
Maximum DC Voltage | 750 VDC | 950 VDC | ||
Start-up Voltage / Initial Feeding Voltage | 220 VDC / 250 VDC | 500 VDC / 550 VDC | ||
MPP Voltage Range | 250 VDC ~ 700 VDC | 550 VDC ~ 900 VDC | ||
Number of MPP Trackers | 1 | |||
Maximum Input Current | 20 Amp | 33 Amp | 48 Amp | |
GRID/UTILITY OUTPUT (AC) | ||||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |||
Output Voltage Range | 184 - 265 VAC per phase | |||
Output Frequency Range | 47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz | |||
Nominal Output Current | 8.7 A per phase | 14.3 A per phase | 29 A per phase | |
Power Factor | > 0.99 | |||
AC INPUT | ||||
AC Start-up Voltage | 120 - 140 VAC per phase | |||
Auto Restart Voltage | 180 VAC per phase | |||
Acceptable Input Voltage Range | 170 - 280 VAC per phase | |||
Maximum AC Input Current | 20 A per phase | 30 A per phase | 40 A per phase | |
BATTERY MODE OUTPUT (AC) | ||||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |||
Output Frequency | 50 Hz / 60 Hz (auto sensing) | |||
Output Waveform | Pure sine wave | |||
Efficiency (DC to AC) | >91% | |||
BATTERY & CHARGER | ||||
Nominal Battery Voltage | 192 VDC | 384 VDC | ||
Maximum Charging Current | 32A | 52A | 50A | |
GENERAL | ||||
PHYSICAL | ||||
Dimension, D X W X H (mm) | 815 x 300 x 830 | 559 x 320 x 909 | 559 x 320 x 909 | |
Net Weight (kgs) | 102 | 115 | 120 | |
INTERACE | ||||
Communication Port | RS-232/USB | |||
Intelligent Slot | Optional SNMP, GRPS, WIFI, Modbus cards available | |||
ENVIRONMENT | ||||
Humidity | 0 ~ 90% RH (No condensing) | |||
Operating Temperature | -10 to 55°C | |||
Altitude | 0 ~ 1000 m** | |||
*These figures are based on VDE-4105 standard. All figures may vary depending on different AC voltage and country requirements. | ||||
** Power derating 1% every 100 m when altitude is over 1000m | ||||
Product specifications are subject to change without further notice |